| Type of Power | Six stard “AA” (IEC LR-6) alkaline batteries |
| Battery Life | 12 hours of field operation |
| Test Frequency | 55 Hz internally generated providing a universal 50/60 Hz test set |
| Turns Ratio Range | 0.8 to 10 |
| Relative huity | Operating: 0 to 90% noncondensing Storage: 0 to 95% noncondensing |
| Protective Devices | High voltage side shorting relay |
| Measuring Time | Less than 5 seconds |
| Measurement Method | ANSI/IEEE C57.12.90 |
| Dimensions | 240 H x 115 W x 50 D mm (9.5 H x 4.5 W x 1.9 D in.) |
| Weight | Approximately 1.3 kg (2.8 lb) |
The Megger TTR20 is an automatic h-held battery operated transformer turns ratio test set. It is used to measure the turns ratio, excitation current polarity of windings in single- three-phase distribution power transformers (tested phase by phase), potential & current transformers, tapped transformers. The unique design of the TTR20 allows the user to operate the test set while holding it in one h. It effectively eliminates the user from having to kneel or bend down to operate the instrument speeds up testing time. Realizing the extreme environments in which the TTR20 must operate, special attention has been paid to making it extra rugged, with a high impact, shock resistant case, yet incredibly lightweight at a mere 870 g (1.9 lbs). Its design makes this instrument well suited for use in a variety of harsh environments. The TTR20 is particularly suited for testing in substations, transformer-manufacturing environments, meter shops. It features a high-contrast, backlit LCD screen which can be seen in bright or ambient light. This unit measures a high turns ratio of 10,000:1 accurately with the lowest excitation voltage. The excellent repeatability of the TTR20 helps the users to determine the condition of transformers under test. It is designed for simple, one button operation with the measured results displayed directly on the easy to read LCD or printed to the optional printer. The TTR20 needs no additional software comes ready to use complete out of the box. APPLICATIONS It it used to determine the no-load accuracy of CTs PTs also determine the need to further test faulty CTs PTs. The TTR20 applies voltage to the high-voltage winding of a transformer accurately measures the resulting voltage from the low voltage winding. The ratio of voltages is directly proportional to turns ratio. In addition, the unit measures excitation current polarity. TRANSFORMER TURNS RATIO Transformer Polarity |
| Type of Power | Six stard “AA” (IEC LR-6) alkaline batteries |
| Battery Life | 12 hours of field operation |
| Excitation Voltage | 8 V rms for testing distribution or power transformers PTs 0.5, 1.5, or 8 V ac rms for testing CTs. The excitation voltage is switched automatically if excitation current exceeds a preset value. |
| Test Frequency | 55 Hz internally generated providing a universal 50/60 Hz test set |
| Excitation Current Range | 0 to 100 mA, 4-digit resolution |
| Turns Ratio Range | 0.8 to 10,000, 5 digit resolution |
| Transformer Polarity | Normal or reversed |
| Current (rms) accuracy | (2% of reading + 1 digit) |
| Turns Ratio Accuracy | 0.1% (0.8 to 2000) 0.15% (2001 to 4000) 0.25% (4001 to 10,000) |
| Display full graphics | LCD module adjustable back-lighting wide temperature range 128 x 64 dots (21 acters by 8 lines) |
| Transformer Winding Phase Relationship | ANSI C57.12.70-1978 |
| Safety/EMC/Vibration | Meets the requirements of IEC-1010-1, CE ASTM D999.75 |
| Temperature Range | Operating: -20º C to 55º C (-5º F to 130º F) Storage: -50º C to 60º C (-55º F to 140º F) |
| Relative huity | Operating: 0 to 90% noncondensing Storage: 0 to 95% noncondensing |
| Protective Devices | High voltage side shorting relay, transient voltage suppressors gas surge voltage protectors |
| Measuring Time | Less than 5 seconds |
| Measurement Method | ANSI/IEEE C57.12.90 |
| Dimensions | 240 H x 115 W x 50 D mm (9.5 H x 4.5 W x 1.9 D in.) |
| Weight | Approximately 1.3 kg (2.8 lb), including leads |